Firebreak grill
- Fire resistance: 60, 120, and 240 minutes
- Airflow up to 80%
- Maximum dimensions:
• – Single round grille – Ø 400 [mm];
• – Single rectangular grille – 600×600 [mm]
• Non-standard sizes
COR CFR GRILLE ventilation grilles are made of a material that expands when exposed to temperatures above 140 °C. Intumescent inserts seal the ventilation openings during a fire, preventing the spread of flames and smoke
APPLICATION:
COR CFR grilles are installed in ventilation openings in walls and floors. The material’s expansion during a fire completely fills the opening, preventing flames and smoke from entering adjacent rooms.
Solid walls:
The wall must be at least 150 mm thick and have a concrete structure, cellular concrete structure, or masonry structure, with a minimum density of 600 kg/m³
Rigid floors:
The floor must be at least 150 mm thick and have a concrete structure, cellular concrete structure, or masonry structure, with a minimum density of 1700 kg/m³

Conector T

Conector X
Installation method:
Model T and Model X connectors are used to connect COR FR GRILLE intumescent rectangular ventilation grilles to one another. The connectors must be secured to the metal enclosure using rivets or steel sheet brackets.